Base Slope, Drain Tile Pitch, and the Outlet
The IRC base slope under the slab, the 1/8 in per foot pitch on the drain tile, the gravel and fabric quantities, the pipe size, and the daylight or sump decision, with the dampproof and below-grade insulation list.
IRC R401.3 asks for a base that extends 10 ft beyond the footing and slopes at 1/4 in per 10 ft. Drain tile runs at 1/8 in per foot to a daylight outlet, a sump, a dry well, or a storm sewer, with 12 in of gravel over a pipe and 2 ft of cover.
How the math works
- Base (IRC R401.3): a base under a slab-on-grade and below a footing extends a minimum of 10 ft beyond the footing, and the base is sloped at a grade of 1/4 in per 10 ft, a 1:400 slope, to a daylight outlet, a sump, a dry well, or an under-slab drainage system. A 10 ft strip at 1/4 in per 10 ft is a 1/4 in drop.
- Drain tile (IRC R401.3.1): a perforated pipe at the footing with the top of the pipe below the bottom of the footing, pitched not less than 1/8 in per foot (1:96) to a daylight outlet, a sump pit, a dry well, or a storm sewer, with a cleanout at the building and every 50 ft, a gravel bed, and 2 ft of cover.
- Site grade (IRC R401.4 and R408): the finished grade slopes away from the wall with at least 6 in of fall over the first 10 ft, with a swale, a berm, and a 2 percent slope on a lot that will not carry the 6 in, the downspout discharged 6 ft from the wall with an above-grade outlet, and 18 in of clearance over the exposed ground in a crawl (IRC R408.1) with 12 in over the joists.
- Dampproof and insulation (IRC R401.1, R401.2, table R402.2.11): the wall below grade is dampproofed on the exterior face, a soil that wicks water to the wall gets the tanking, and a conditioned basement wall gets the below-grade continuous insulation by climate zone in the table: 1 in of rigid in the mild zones and 2 in in the cold zones, with the vapor barrier under the slab over a 4 in gravel base.
- Sump and discharge: a sump pit at the low point with a solid cover, a pump with a float, a check valve, a battery backup, an alarm, an air gap at the discharge, a 6 in weep hole at the pit, a discharge line above the frost line pitched 1/8 in per foot to daylight, and a storm tie-in with a cleanout and an air gap. A sump on a power loss is a wet basement, and a battery backup is part of the system rather than an accessory.
What slope does a foundation drain need?
The IRC asks for 1/8 in per foot (1:96) on the perforated pipe at the footing, and 1/4 in per 10 ft (1:400) on the base under the slab with the base extending 10 ft beyond the footing. A 60 ft run at 1/8 in per foot is a 7.5 in drop, and a 10 ft base strip at 1/4 in per 10 ft is a 1/4 in drop.
Does drain tile need gravel?
The field build is a 12 in wide trench with the pipe at the footing, 6 in of clean 3/4 in gravel over the pipe, geotextile fabric over the stone and down the trench walls, and 2 ft of cover. A gravel trench with no fabric plugs in a few years, and clean stone with no fines is the void that drains.
Does my basement need a sump pump?
A sump is one of the four outlets the IRC lists, with a daylight outlet, a dry well, and a storm sewer, and a sump is the answer on a flat lot with no daylight run. The sump build: a pit at the low point with a solid cover, a pump with a float, a check valve, a battery backup, an alarm, an air gap at the discharge, a weep hole at the pit, and a discharge line above the frost line pitched to daylight.
How far away do I slope the grade?
6 in of fall over the first 10 ft from the wall, with a swale, a berm, and a 2 percent slope on a lot that will not carry 6 in of fall, and the downspout discharged 6 ft from the wall with an above-grade outlet (IRC R401.4). A grade that stops at 3 ft of fall is the grade that fills the gravel trench on every rain.