Mold Containment Class, Scrubber CFM, and PPE

The IICRC S520 containment classes, the plastic build, the air-scrubber size in air changes per hour, the negative pressure target, the PPE level, and the disposal and clearance sequence for a remediation job.

Containment class comes from area and category: Class 1 under 10 sq ft, Class 2 from 10 to 100 sq ft, Class 3 over 100 sq ft, a plenum, and a Category 3 job. Scrubbers are sized to 4 to 6 air changes per hour inside the containment.

—Containment class and category
—Plastic build and decon chamber
—Scrubber CFM and negative pressure
—Respirator, suit, and PPE level
—Bagging and disposal
—Removal, drying, and clearance
How the math works
  • Categories and classes (IICRC S520): water Category 1 is clean water, Category 2 carries a significant contaminant, Category 3 is grossly contaminated sewage and flood water. Containment Class 1 is a spot under 10 sq ft, Class 2 is 10 to 100 sq ft, a wall, a cavity, Class 3 is over 100 sq ft, a plenum, a cavity system, a Category 3 job, and the class governs the enclosure, the PPE, the filtration, and the clearance.
  • Containment build: 6-mil plastic over the floor with a 6 ft lap past the work, taped seams with 12 in laps, plastic 6 ft up the walls on a Class 2 enclosure, plastic to the ceiling on a Class 3 enclosure, a decon chamber at the entry with a zipper, the HVAC openings taped, the door sealed, and the containment in place until the clearance pass.
  • Filtration: HEPA air scrubbing sized to 4 to 6 air changes per hour of the containment volume, negative pressure on a Class 3 enclosure with the scrubber exhausting outside the enclosure and make-up air at the far zipper, local exhaust at the cut, a shrouded HEPA vacuum for the surfaces, and no unfiltered air to the occupied space.
  • PPE (S520 Annex M): Class 1 takes an N95, eye protection, and gloves; Class 2 takes a half-face or full-face respirator with P100 filters, a coverall, gloves, and eye protection; Class 3 takes a full-face powered air-purifying respirator with HEPA filters, a hood, a taped suit, boot covers, doubled gloves, and a doff sequence in the decon chamber.
  • Disposal: bag in 6-mil plastic inside the containment, seal and wipe the outside of the bag before the bag leaves, dispose under local construction and debris rules, sewage-contaminated material handled to the local Category 3 rule, and the disposal receipt, the manifest, and the disposal record kept in the job file.
Planning tool on the IICRC S520 standard for professional mold remediation and the S500 water damage standard, with the EPA mold clean-up guidance for large areas. The S520 classes and the air-change band are the standard text, and a containment plan signed by a licensed industrial hygienist, a post-remediation verification by a third party, a state remediation license, a local permit, and a building department inspection rule are jurisdiction and contract calls. A plenum, an air handler, an insulated duct liner, a cooling coil, a septic backup, a sewage flood, a black water category, a mycotoxin question, a building with a health complaint, and a litigation file all go past a calculator, and a person with a health condition is the reason the clearance test exists.

What are the mold containment classes?

Class 1 is a spot under 10 sq ft: no full enclosure, a plastic floor drop, and light PPE. Class 2 is 10 to 100 sq ft, a wall, a cavity: a poly enclosure 6 ft up the walls, a decon chamber, HEPA scrubbing, and P100 respirators. Class 3 is over 100 sq ft, a plenum, a cavity system, and a Category 3 job: full containment to the ceiling, negative pressure, a double decon chamber, and a powered air-purifying respirator (IICRC S520).

How many air changes per hour does a containment need?

4 to 6 air changes per hour of the containment volume, sized with a HEPA scrubber: a 10 ft by 8 ft by 8 ft room is 640 cu ft, so 43 to 64 cfm, and the scrubber runs continuous through the work. Class 3 enclosures run negative, exhausted outside the enclosure, with make-up air at the far zipper.

What respirator do the crew need?

Class 1 takes an N95 with eye protection and gloves, Class 2 takes a half-face or full-face respirator with P100 filters, a coverall, gloves, and eye protection, and Class 3 takes a full-face PAPR with HEPA filters, a hood, a taped suit, boot covers, and doubled gloves (S520 Annex M).

When is the job done?

The removal is complete, the drying is complete, and the visual is clean: no dust, no debris, no moisture, and the material moisture readings are within 1 percent of the dry standard taken from an unaffected reference surface in the same building. Class 2 and Class 3 jobs end with the containment down after that pass, and a client can ask for a tape-lift, a dust wipe, and an air sample.