Fixture Units & Supply Size

Fixture units by fixture count, the demand curve that converts them to gallons per minute, and the supply pipe and meter size that carries it at 8 feet per second.

A 3 fixture unit fixture does not mean 3 gpm: a 10 fixture-unit house draws about 14 gpm at peak, and 25 fixture units draws 24 gpm, because not every faucet runs at once.

—Total water supply fixture units
—Peak demand from the curve (GPM)
—Supply size at 8 fps (inches)
—Water meter size recommendation
—Fixture branch + heater connections
—Hot water branch and recirculation
How the math works
  • Fixture units (IPC Table 702.3, private/residential values): water closet flush tank 2.1, lavatory 1.1, kitchen sink 2.0, shower head 3.0, clothes washing machine 2.0, dishwasher 2.0, floor sink and hose bibb 2.0. Public fixtures run 3 to 6, and a service sink is 2.
  • Demand curve (IPC Table 703.1, one-family values): 10 FU = 14 gpm, 15 = 18, 20 = 22, 25 = 26, 30 = 29, 40 = 36, 50 = 42, 60 = 47, 80 = 56, 100 = 65, 150 = 87, 200 = 110. Fixture units are a diversity model, not an addition: a 10 FU house is 14 gpm, not 10.
  • Pipe size: size the main at 8 feet per second (velocity limit that keeps noise and erosion down in copper), so required area = gpm × 0.002228 ÷ 8 sq ft. A 24 gpm demand needs 0.677 in ID: 3/4 in copper (0.773 in).
  • Fixture branches: 1/2 in for a water closet flush tank (1/2 in for flushometer with 1.6 gpf), 3/4 in for a shower (a 2.5 GPM head needs 3/4 to keep pressure at 8 psi residual), 1 in for a tub-shower combo, 3/4 for kitchen and laundry.
  • Water service: the 2026 residential meter is 3/4 in for a 20 gpm peak, 1 in for 40 to 90, and the service line is sized from the main to the meter at the same velocity rule, with a 1 in service line standard in frost country.
Sizing on the IPC fixture-unit method, which sizes for peak simultaneous demand with diversity built in. Available main pressure, the residual 8 psi fixture minimum (flushometer fixtures want 15 psi), fire-flow demands on a combination system, backflow device pressure drop, PEX sizing (which wants a C-value method, not velocity), and the 20 in water-heater intake distance in the plumbing code all change the answer.

How many fixture units is a one-bathroom house?

A bathroom group (water closet 2.1, lavatory 1.1, tub-shower 3.0) plus a kitchen sink 2.0 and a laundry 2.0 = 8.2 fixture units, which is about 12.5 gpm of peak demand and a 3/4 in supply line.

What size water service line for a house?

A typical 3 fixture bathroom + kitchen + laundry house lands at 24 to 30 fixture units and 26 to 29 gpm, which needs 1 in copper ID at 8 fps: a 1 in meter socket and a 1 in service line is the standard residential answer, and 3/4 in is the minimum in the code for a dwelling.

Does a shower need 1/2 inch pipe?

No. A 2.5 GPM shower head at 1/2 in pipe at 8 fps needs more than 1 psi to move, and fixture minimums are 8 psi: 3/4 in is the code answer for a shower, and a 2 gpm pressure-balance valve at 3/4 in is the reason showers in 1/2 in lines feel weak.